777-FT - 777 MRSW Series

Littelfuse Remote Indication and Monitoring
Roll Over to Zoom
The 777 Manual Remote Reset Kit allows the 777 line of motor and pump protection products to be manually reset without opening the panel door. Simply connect the 9-pin adapter to the 777 communication port and mount the push-button switch in a convenient location.
Property (Mouseover for details) Value
Input Voltage (V) 200 - 480VAC
Maximum Input Power 10W
Output Form SPDT - Form C
Output Load Rating (VA) Pilot Duty: 480VA @ 240VAC B300; General Purpose: 10A @ 240VAC
Full Load Amp Range (A) 2 - 25A 3 phase (loops required); 25 - 90A 3 phase (direct); 80 - 800A 3 phase (external CTs)
Timing Accuracy (%) 5% ±1s
Rapid Cycle Timer (s)
Restart Delay Range
Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 amps direct)
Trip Delay Type
Overvoltage Trip Voltage (%) LV setting - 528V
Undervoltage Trip Voltage 170V - HV setting
Voltage Unbalance Trip Point (%) 2 - 15% or 999
Voltage Accuracy (%) ±1%
Overcurrent Trip Point (20A - 100A) … MULT of 80 - 120% of CT primary
Overcurrent Trip Class
Undercurrent Trip Point (0 10 - 98 Amps) … MULT or 40 - 100% of CT primary
Undercurrent Trip Delay (s) 2 - 60s
Current Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
Current Unbalance Trip Delay (s) % over setpoint / Trip time: 1% / 30s; 2% / 15s; 3% / 10s; 4% / 7.5s; 5% / 6s; 6% / 5s; 10% / 3s; 15% / 2s
Current Accuracy (%) ±3% (<100 amps direct)
Ground Fault Current Trip Point (A) (3 - 20A) … MULT or 10 - 30% of primary CT or OFF
Ground Fault Trip Delay (s) % of setpoint / Trip time: 101 - 200% / 8s ± 1s; 30s; 201 - 300% / 4s ± 1s; 301 - 400% / 3s ± 1s; 401%+ / 2s ± 1s
Ground Fault Accuracy (%) ±15%
Sensor Hole Size Max conductor size: 0.65 in (with insulation)
Motor Acceleration Time Operating Point (s)
Short Circuit (kA) 10kA
Surge Protection IEC: 61000-4-5 Level 3 2kV line-to-line; Level 4 4kV line-to-ground
Protection Class IP20
Pollution Degree 3
CT Ratio 1 - 10 conductors or 100 - 800 ratio
Address A01 - A99
Life Electrical: 1 x 105 operations at rated load; Mechanical: 1 x 106
Termination Type Torque: 7in-lbs
Mounting Method Surface mount (4 - #8 screws) on DIN rail mount
Operating Temperature -20° to 70°C (-4° to 158°F)
Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
Humidity 10-95% non-condensing per IEC 68-2-3
Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g) 1.56 lbs. (25.0 oz. 707.6 g)
To request product environmental information, please complete the Product Environmental Information Request Form.