777-FT - 777 Series

Series: 777
Questions? Contact Littelfuse Support
External overview image
Roll Over to Zoom
The 777 Manual Remote Reset Kit allows the 777 line of motor and pump protection products to be manually reset without opening the panel door. Simply connect the 9-pin adapter to the 777 communication port and mount the push-button switch in a convenient location.
Property (Mouseover for details) Value
Input Voltage (V) 200 - 480 Vac
Maximum Input Power 10
Input AC Line Frequency (Hz) 50 / 60
Output Form SPDT - Form C
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
Full Load Amp Range (A) 2 - 25: 3 phase (looped conductors required); 25 - 90: 3 phase (direct); 80 - 800: 3 phase (external CTs)
Timing Accuracy (%) 5% ±1 s
Rapid Cycle Timer (s)
Restart Delay Range
Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct)
Trip Delay Type
Overvoltage Trip Voltage (%) LV setting - 528 V
Undervoltage Trip Voltage 170 V - HV setting
Voltage Unbalance Trip Point (%) 2 - 15% or 999
Voltage Accuracy (%) ±1%
Overcurrent Trip Point (20 - 100 A) … MULT of 80 - 120% of CT primary
Overcurrent Trip Class
Undercurrent Trip Point 0; 10 - 98 A … MULT or 40 - 100% of CT primary
Undercurrent Trip Delay (s) 2 - 60 s
Current Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
Current Unbalance Trip Delay (s) % over setpoint / Trip time: 1% / 30s; 2% / 15s; 3% / 10s; 4% / 7.5s; 5% / 6s; 6% / 5s; 10% / 3s; 15% / 2s
Current Accuracy (%) ±3% (<100 A direct)
Ground Fault Current Trip Point (A) (3 - 20) … MULT or 10 - 30% of primary CT or OFF
Ground Fault Trip Delay (s) % of setpoint / Trip time: 101 - 200% / 8s ± 1s; 30s; 201 - 300% / 4s ± 1s; 301 - 400% / 3s ± 1s; 401%+ / 2s ± 1s
Ground Fault Accuracy (%) ±15%
Sensor Hole Size Max conductor size: 0.65 in (with insulation)
Motor Acceleration Time Operating Point (s)
Short Circuit (kA) 10
Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
Protection Class IP20 (finger safe)
Pollution Degree 3
CT Ratio 1 - 10; or 100 - 800 ratio
Address A01 - A99
Termination Type Torque: 7 in-lbs
Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature -20° to 70°C (-4° to 158°F)
Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
Humidity 10 - 95% non-condensing per IEC 68-2-3
Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.