777-MV-P2 - 777 Series

Series: 777
Questions? Contact Littelfuse Support
External overview image
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The 777-MV-P2 three-phase current and voltage monitor provides motor protection with input voltage from 100–240 V ac and motor full load ampere range of 10–800 A (external CTs required).

Property (Mouseover for details) Value
Input Voltage (V) 100 - 240 Vac
Maximum Input Power 10
Input AC Line Frequency (Hz) 50 / 60
Output Form SPDT - Form C
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
Full Load Amp Range (A) 10 - 800 (external CTs required)
Timing Accuracy (%) ±0.5 s
Rapid Cycle Timer (s) 0 - 999 s
Restart Delay Range All faults except undercurrent: 2 - 500 m; Undercurrent: 2 - 500 m A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct)
Overvoltage Trip Voltage (%) 86 - 264 V
Undervoltage Trip Voltage 85 - 262 V
Voltage Unbalance Trip Point (%) 2 - 25% or 999 (disabled)
Voltage Accuracy (%) ±1%
Overcurrent Trip Point 80 - 140% of CT primary
Overcurrent Trip Class 02 - 60; J02 - J60; L00 - L60; or OFF
Undercurrent Trip Point 40 - 140% of CT primary
Undercurrent Trip Delay (s) 2 - 999 s (default)
Current Unbalance Trip Point (%) 2 - 50% or 999 (disabled)
Current Accuracy (%) ±3% (<100 A direct)
Ground Fault Current Trip Point (A) 6 A - 40% of CT primary or OFF
Ground Fault Accuracy (%) ±15%
Sensor Hole Size Max conductor size: 0.65 in (with insulation)
Short Circuit (kA) 100
Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
Protection Class IP20 (finger safe)
Pollution Degree 3
CT Ratio 25; 50; 75; 100; 150; 200; 300; 400; 500; 600; 700; 800
Address COM: C00 - C07; RS485: A01 - A99
Termination Type Torque: 7 in-lbs
Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature -20° to 70°C (-4° to 158°F)
Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
Humidity 10 - 95% non-condensing per IEC 68-2-3
Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.