FPS-CTU-01-00 - FPS Series

Series: FPS
Questions? Contact Littelfuse Support
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The FPS (Feeder Protection System) is a feeder-protection relay that provides current, voltage, and temperature protection for feeder applications. It offers integrated breaker or contactor control, data logging, and a complete metering package. The FPS is typically used in processing, manufacturing, petroleum, chemical, mining, forestry, water, and waste treatment applications.

Features & Benefits:

  • Eighteen protective functions to extend the life of transformers and feeder cables
  • Meters current, voltage, power, temperature, and more
  • Inverse-time (including IEC and IEEE curves) and definite-time overcurrent and earth-fault protection
  • Breaker or contactor control - integrated OPEN and CLOSE command keys
  • Large 80-character vacuum-fluorescent display
  • Eight digital inputs, five relay outputs, one analog input and output
  • RTD module can be installed remotely (up to 1,200 m) to simplify wiring
  • CSA Class 1 Zone 2 hazardous-location certified OPI and RTD modules
  • Standard Modbus RTU and Allen-Bradley DF1 RS-485 communications
  • Optional Modbus TCP and Ethernet/IP, DeviceNet, PROFIBUS communications
  • Free SE-Comm-RIS PC-interface software
  • Conformally coated circuit boards
  • 10-year warranty
Property (Mouseover for details) Value
Analog Output Current mA 4 - 20
Communications RS/TIA-485
Relay Contacts Config 3 Form A (N.O.); 2 Form C (N.O./N.C.)
Supply Voltage ac 65 - 265
Supply Voltage dc 80 - 275
IEEE Device Numbers 1 - 2 - 3 - 5 - 19 - 27 - 37 - 38 - 46 - 47 - 49 - 50 - 50G - 50N - 51 - 51G - 51N - 55 - 59 - 74 - 81 - 86 - 94
Relay Contacts Operation Fail-safe / Non Fail-safe
Weight (lbs/g) 0 Kg
Analog Inputs One 4-20 mA
Conformally coated Standard
Frequency 50; 60; ASD
GF Trip Level Range pct 5 - 100% of CT-Primary Rating
GF Trip Time s 0.0 - 100.0
Harmonic Filtering Standard (DFT)
Reset Type Front-panel switch/Remote N.O. Contact
Temp Sensor Config Up to 8 with MPS-RTD
Digital Inputs 8
To request product environmental information, please complete the Product Environmental Information Request Form.